VGET™ TU晶闸管开关功率单元

发布日期:2016/11/9 浏览次数:1261

 

Film capacitors – Power Factor Correction

薄膜电容器-功率因数校正

Key components – Thyristor switched power unit VGETTU

关键部件-晶闸管开关功率单元VGETTU

Series/model系列/型号:VGET™-TU-                 

Date      日期:  June 2014 20146 Version版本: 3

VGET™-TU series of SCR non-contact switching power unit is an electronic power device capable of fast switching of an electric parallel capacitor. The electrical structure is mainly composed of a high-power anti-parallel connected SCR unit, an isolation circuit, a trigger circuit, a synchronization circuit protection circuit and a driving circuit, And is provided with a connection terminal for controlling the switching to turn-on or off. The control logic voltage OV(off) , 12V (on). Applicable to the change in the load faster occasions.

VGET™-TU系列可控硅无触点开关功率单元是一种能够对电力并联电容器进行快速投切的电子型功率器件模块,其电气结构主要由大功率反并连可控硅单元、隔离电路、触发电路、同步电路保护电路及驱动电路组成,并配有控制开关导通或截止的接线端子。控制逻辑电压OV(截止)、12V(导通)。适用于在负荷变化较快的场合。

 

VIGOR  AG 2014. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without VIGOR' prior express consent is prohibited.

VIGOR公司2014. VIGOR没有事先明确同意对本刊物的复制,出版和传播,包括本文的附件以及其中包含的信息是被禁止的。

Characteristics特点     

n Fast electronically controlled thyristor switch with status display

快速电子控制的具有状态显示的晶闸管开关

n To configure Big power high-frequency SCR, At the Both ends of SCR in the positive and negative repetitive peak voltage VDRM maximum: 2400V

配置大功率高频可控硅可控硅两端的正反向重复峰值电压VDRM的最大值为:2400V

n For capacitive loads up to 90 kvar

对于容性负载高达90千乏

n Suitable of the dynamic PFC-systems in 230 to  690 V grids for designing

适用于在230690 V电网的动态PFC系统设计 

n Using high-speed PLC control accurately capture for the zero crossing point of the voltage across of  the two ends of the SCR unit

使用高速PLC控制精确捕获SCR单元两端电压的过零点

n No system perturbation due to switching operations  (transients)

开关操作(瞬态)无系统扰动 

n Maintenance-free免维护 

n Long useful service life长期有效使用寿命 

n No noise emission during switching operation开关操作时无噪音 

n Compact module ready for connection 紧凑型模块,可以直接连接

 

Features 特征

n Easy installation: mechanical assembly directly on a mounting plate

安装简便:在安装板上直接机械装配 

n Optimized switching behaviour to the connected load (tuned/detuned) via the internal processor

通过内部处理器为所连接的负载(调谐/失谐)优化切换行为 

n Mounting position upright or Horizontal installation; minimum 100 mm space both of the inlet and outlet sides

安装位置竖直向上或水平安装进线和出线两侧的最小空间100 mm 

n Display and control via LED display 通过LED显示和控制  

- Power电源

- Operation 操作

- Faults故障 

- Activation激活 

n Permanent self-monitoring永久性自我监测   

- Voltage电压 

- Operating state运行状态 

 

n  Model Description型号说明

 

VGET™Trademarks公司商标-TUIndicates of Thyristor Switching power unit 表示晶闸管开关功率单元-Qn- Indicates Rated Output Power表示额定输出功率kavr-G- Indicate Three-phase total compensation or F- Indicate single-phase separately compensation. G-表示三相共补F-表示单相分补/VV-Indicates the applicable grid voltage表示适用的电网电压 /HzHz-Indicates the applicable grid frequency表示适用的电网频率

Note注释

GRepresentative of Three-phase total compensation 代表三相共补

FRepresentative of single-phase separate compensation 代表单相分补

 

List of models型号列表

 

 

230V 50Hz/60 Hz Thyristor switch power unit Suitable for single-phase separate compensation
230V 50Hz/60 Hz适用于单相分补的晶闸管开关功率单元

Model specification
型号规格

Rated voltages VR
额定电压VR
V

Output Power Qn
输出功率Qn
Kvar

Dimensions
外形尺寸
(W x H x D) mm

VGET™-TU-30-F/230V

230V

40

159 × 200 × 170 mm

VGET™-TU-60-F/230V

230V

60

202 × 222 × 190 mm

 

400V 50Hz/60 Hz Thyristor switch power unit Suitable for Three-phase total compensation
400V 50Hz/60 Hz适用于三相共补的晶闸管开关功率单元

Type specification
型号规格

Rated voltages VR
额定电压VR
V

Output Power Qn
输出功率Qn 
Kvar

Dimensions
外形尺寸
(W x H x D) mm

VGET™-TU-60-G/400V

400V

60

159 × 200 × 170 mm

VGET™-TU-90-G/400V

400V

90

202 × 222 × 190 mm

 

Max Dimensions 最大外形尺寸

202 × 222 × 190 mm (w × h × d)

Weight  Kg重量

Approx.  kg  

Rated voltage UR 额定电压

230 … 400 …690V

Maximum voltage最大电压

  1. in conventional PFC-systems (without reactors)

在常规的PFC系统(无电抗器)

  1. in detuned PFC-systems (7 % detuning)

在失谐的PFC系统(7%失谐)

  1. in detuned PFC-systems (14 % detuning)

在失谐PFC系统(14%失谐)

 

440 V

440 V (no upwards tolerance permitted没有向上的允许公差)
440 V

Frequency FR 频率 

50/60 Hz

Switching capability切换容量 

Nominal output 30 kvar at 230 V
在230 V额定输出30千乏
Max. 40 kvar at 400 V with ambient temperature <40 °C
最大40千乏在230 V以及环境温度<40℃

Nominal output 50 kvar at 230 V
在230 V额定输出50千乏
Max. 60 kvar at 400 V with ambient temperature <40 °C
最大60千乏在230 V以及环境温度<40℃

Nominal output 50 kvar at 400 V
在400 V额定输出50千乏
Max. 60 kvar at 400 V with ambient temperature <40 °C
最大60千乏在400 V以及环境温度<40℃

Nominal output 75 kvar at 400 V
在400 V额定输出75千乏
Max. 90 kvar at 400 V with ambient temperature <40 °C
最大90千乏在400 V以及环境温度<40℃

Activation激活 

10 … 24 V DC (approx. 4 mA) via terminal clamp, internally electrically isolated
10 ...24 V DC(约4 mA)通过端子钳,内部电气隔离

Full response time全响应时间

Approx. 20 ms 约20毫秒

Display显示 

4 status LEDs per phase: operation/fault and triggering signal
1个电源指示灯,3个LED状态指示灯

Power circuit电源电路

Direct connection 4 pole via terminal clamps  
(D = 6 mm2 resp. 4 mm2),
Connection: up and down
通过端子钳直接连接4极(D = 6 mm2 resp. 4 mm2), 连接方式:上进下出

Power dissipation功耗

PD (in W) = 2.0 × I (in A);                                         at 400 V/90 kvar  approx. 350 W  

Fuses (mandatory for protection of components) 保险丝(强制性的保护部件) 

3 × electronic fuse „superfast“    
NH00 AC 400 V, characteristic gRL
90 kvar: 200 A 
3×电子保险丝“超快”NH00交流690 V,特点gRL90kvar:200 A

Ambient operating temperature at nominal load
额定负载下的工作环境温度

–25 °C … +85 °C

Cooling 冷却

forced air cooling 强制通风冷却

Humidity 湿度

Max.95%

Altitude 海拔

Max.4000m

Degree of protection防护等级

IP20

Dimensional drawing 尺寸图

Cautions and Warnings General警告和一般提醒
•Thyristor power units TU series may only be used for the purpose they have been designed for.
TU系列晶闸管功率单元仅可用于设计。
•Thyristor power units TU series may only be used in combination with appropriate pre-switched grid separator device.
TU系列晶闸管功率单元只能与适当的预切换电网分离器装置结合使用。
•Thyristor power units have to be projected in such a way that in case of any failure no uncontrolled high current and voltages may occur.
晶闸管功率单元必须考虑到在任何故障的情况下不会出现不受控制的高电流和电压这样的情况。
•The devices in operation have to be protected against moisture and dust, sufficient cooling has to be assured.
操作中的设备必须防止潮湿和灰尘,必须确保充分的冷却。
 
Attention注意
Due to the switching principle of the thyristor power unit the power capacitors are permanently loaded to the peak value of the grid voltage (DC voltage) even when switched off.
由于晶闸管功率单元的投切原理,即使在关断时,电力电容器也长期地加载在电网电压(直流电压)的峰值。
Therefore following rules have to be obeyed in any case
因此,在任何情况下必须遵守以下规则:
•For standard PFC-systems (without reactors) power capacitors of 440 V nominal voltage have to be used; for detuned systems PFC capacitors of 480 V nominal voltage have to be used.
对于标准PFC系统(无电抗器),必须使用440 V标称电压的电力电容器; 对于失谐系统,必须使用480 V额定电压的PFC电容器。
•Due to the high voltage (2 x peak value of nominal voltage) that occurs, the discharge resistors of the power capacitors have to be replaced by special types (1 x accessory EW22).
由于发生高电压(2 x标称电压峰值),电力电容器的放电电阻必须替换为特殊类型(1 x附件EW22)。
•In dynamic systems with TSM power units no fast discharge reactors may be used (reactor = DC wise short circuit).
在具有TU功率单元的动态系统中,不能使用快速放电反应器(反应器=直流短路)。
•For standard PFC-systems 2 current limiting reactors are mandatory per thyristor power unit (2 x BD050 or 2 x BD100).
对于标准PFC系统,每个晶闸管功率单元必须要2个限流电抗器(2个BD050或2个BD100)。
•Thyristor power unit in general have to be protected by superfast electronic fuses. Principles for dimensioning have to be considered. Fuses in the system have to be marked.
晶闸管功率单元通常必须由超快速电子保险丝保护。 必须考虑尺寸标注的原则。 系统中的保险丝必须标记。
•Due to the special switching, the PFC capacitors are fully loaded even when the particular step has been switched off. Protection against contact has to be guaranteed. Warning signals in the systems are required.
由于投切的特殊,PFC电容器即使通过特定的步骤已关闭时也是完全加载的。 必须保证防止接触。在系统报警信号是必需的。
•Even in switched off state no electrical isolation is achieved for electronic switches. Therefore parts of the systems may not be touched after switching off the complete system before the capacitors have been completely discharged.
即使在关闭状态下没有电气隔离是电子开关来实现的。因此,在整个系统关闭之后电容器完全放电之前系统的部分可能不能触摸。
 
FAILURE TO FOLLOW CAUTIONS MAY RESULT, WORST CASE, IN PREMATURE FAILURES OR PHYSICAL INJURY.
未能遵守注意事项可能导致,最严重的情况,造成故障或身体受伤。
 
Note注意
For detailed information about PFC capacitors and cautions, refer to the latest version of VIGOR PFC Product Profile.
有关PFC电容器和注意事项的详细信息,请参考最新版本的VIGOR PFC产品简介。
 

 